Supplementary Functions
13-4
Current value update data area (Unit memories)
Axis
no.
Unit
memory no.
(Hex)
Name Default Description
Axes
1-16
UM 00590
Current
value
update
request
H0
Only when the corresponding bit for each axis changes to 1 from
0, the current value coordinate controlled by FP7 MC Unit are
changed to the current value update coordinate. After the change,
FP7 MC Unit clears the corresponding bits to 0 automatically.
bit Name Description
0
Axis 1+16n: Current value
update request
0: No change
1: Update the current value
after unit conversion of a
target axis
1
Axis 2+16n: Current value
update request
2
Axis 3+16n: Current value
update request
3
Axis 4+16n: Current value
update request
4
Axis 5+16n: Current value
update request
5
Axis 6+16n: Current value
update request
6
Axis 7+16n: Current value
update request
7
Axis 8+16n: Current value
update request
8
Axis 9+16n: Current value
update request
9
Axis 10+16n: Current value
update request
10
Axis 11+16n: Current value
update request
11
Axis 12+16n: Current value
update request
12
Axis 13+16n: Current value
update request
13
Axis 14+16n: Current value
update request
14
Axis 15+16n: Current value
update request
15
Axis 16+16n: Current value
update request
Axes
17-32
UM 00591
Axes
33-48
UM 00592
Axes
49-64
UM 00593
Virtual
axes 1-
16
UM 00594
Virtual
axes
17-32
UM 00595
Axis 1
UM 005A0
- UM 005A1
Current
value
update
coordinate
K0
Stores the coordinate value to be preset as the current value after
unit conversion.
Range: -2,147,483,648 to 2,147,483,647
The ranges vary depending on the unit settings as below.
pulse: -2,147,483,648 to 2,147,483,647 pulses
μm (0.1μm): -214,748,364.8 to 214,748,364.7 μm
μm (1μm): -2,147,483,648 to 2,147,483,647 μm
inch (0.00001 inch): -21,474.83648 to 21,474.83647 inches
inch (0.0001 inch): -214,748.3648 to 214,748.3647 inches
degree (0.1 degree): -214,748,364.8 to 214,748,364.7 degrees
degree (1 degree): -2,147,483,648 to 2,147,483,647 degrees
An integer equivalent to the current value after unit conversion is
set to the unit memories.
Example) When the unit is μm (0.1 μm), set to "10000" for making
it be 1,000.0 μm.
Axis 2
UM 005A2
- UM 005A3
Virtual
axis 1
UM 00620
- UM 00621
-
Virtual
axis 32
UM 0065E
- UM 0065F
(Note 1): Request signals for 16 axes are allocated to each area (1 word) of current value update request. When the
value of each bit is 1, it turns on. When the value of each bit is 0, it turns off.
bit no.
15
0
8 7
9 1816
Axis no.
25 172432
41 334048
57 495664
(Note 2): As for the unit memory in which the current value update coordinate is set, 2-word area is allocated for each
axis.