Specifications
16-42
16.5.9 Positioning Control Area
: Available, -: Not available
Axis no.
Unit
memory
no. (Hex)
Name Default Description R W
1 UM 009F0
Positioning
repeat count
U0
Set the number of times for repeating the
operation from the positioning control starting
table number until the E-point control.
Range: 0 to 255
When setting 0 or 1, the operation is executed
only once.
When setting 255, the operation is repeated
unlimitedly until the operation is stopped.
(2-64
Virtual 1-32)
UM 009F1
-UM 00A4F
The following areas are allocated to each axis.
Positioning repeat count: 1 word
-
UM 00A50
-UM 00A8F
Reserved for