Specifications
16-46
●: Available, -: Not available
Axis no.
Unit
memory
no. (Hex)
Name Default Description R W
1 UM 01740
No. of
occurrences
of warnings
U0
Annunciates the number of occurrences of
warnings on the 1st axis.
-
1 UM 01741
Reserved for
system
- - - -
1
UM 01742
-UM 01743
Warning code
Buffer 1
H0
Stores the latest warning code (8-digit hex)
from the buffer 1 in order.
-
1
UM 01744
-UM 01745
Warning code
Buffer 2
H0
1
UM 01746
-UM 01747
Warning code
Buffer 3
H0
1
UM 01748
-UM 01749
Warning code
Buffer 4
H0
1
UM 0174A
-UM 0174B
Warning code
Buffer 5
H0
1
UM 0174C
-UM 0174D
Warning code
Buffer 6
H0
1
UM 0174E
-UM 0174F
Warning code
Buffer 7
H0
1
UM 01750
-UM 01751
Warning code
Buffer 8
H0
1
UM 01752
-UM 0175F
Reserved for
system
- - - -
(2-64
Virtual 1-32)
UM 01760
-UM 0233F
As well as the area for axis 1, 32-word area is allocated to each axis in the
following configuration.
Number of occurrences of warnings: 1 word
Reserved area for the system: 1 word
Warning code buffer: 2 words x 8
Reserved area for the system: 14 words
-
-
UM 02340
-UM 0238F
Reserved for
system
- - - -
(Note 1): As for the unit memories in which warning codes are stored, 2-word area is allocated for each axis.
(Note 2): The difference between the unit memory number of the target axis number and the unit memory number of
the adjacent axis number is H20 (for 32 words).