4.4 Setting of Network Configuration
4-13
5. Select "Scan EtherCAT Network" from the context menu.
FP7 MC Unit executes scanning the network. The information on Servo Amplifiers
A6B/A5B connected to FP7 MC Unit is displayed in the project explorer in the
connection order.
• It takes approximately 10 seconds for one axis to complete the scanning of
EtherCAT network.
• "Scan EtherCAT network" can be executed when the "EC L/A" LED on FP7
MC Unit is lit or blinking. Possible situations are as follows.
Unit state and network scanning operation
LEDs of FP7 MC Unit
Possible case and confirmation method
Network
scanning
EC L/A EC RUN ERR
ON OFF ON
”Network configurations verify error” occurs. In this case,
even when the ERR LED is lit, the network scanning can
be executed.
This error also occurs when using FP7 MC Unit for the
first time as the information on the network configuration
is not downloaded to FP7 MC Unit.
Executable
Flickering ON ON
"Network configurations verify error" may occur as the
rotary switches on Servo Amplifier A6B/A5B are not set to
"00". Set the rotary switches to "00" and restart the power
supply.
Not
executable
ON or
Flickering
ON OFF
The situation that the network configuration information
has been downloaded and the number of connected
servo amplifiers matches is possible. The network
scanning can be executed.
Executable