Parameter Descriptions 2-57
7000-TD002A-EN-P – September 2007
Speed Command Minimum [Speed Cmd Min]
Linear Number: 293
Default Value: 6.0 Hz
Minimum Value: 0.0 Hz
Maximum Value: 120.0 Hz
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the minimum value of the Speed Command. When the drive is running, the
absolute value of the Speed Command (which is obtained from the active Reference Command, either
Local, Remote, or Digital) is limited by this parameter and the Speed Command will not drop below this
level regardless of any of the Reference Command Min levels.
Speed Command Maximum [Speed Cmd Max]
Linear Number: 290
Default Value: 60.0 Hz
Minimum Value: 0.0 Hz
Maximum Value: 120.0 Hz
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the maximum value of the Speed Command. When the drive is running, the
absolute value of the Speed Command (which is obtained from the active Reference Command, either
Local, Remote, or Digital) is limited by this parameter and the Speed Command will not exceed this level
regardless of any of the Reference Command Max levels.
Reference Command Potentiometer Min [RefCmd Pot Min]
Linear Number: 41
Default Value: 6.0 Hz
Minimum Value: -120.0 Hz
Maximum Value: 120.0 Hz
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the minimum value of speed command in Hz that could come from the
potentiometer mounted on the door. Along with RefCmd Pot Max (42) this parameter is used in
determining the slope for interpolating the speed command coming from the potentiometer.
Reference Command Potentiometer Max [RefCmd Pot Max]
Linear Number: 42
Default Value: 60.0 Hz
Minimum Value: 0.0 Hz
Maximum Value: 120.0 Hz
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the maximum value of speed command in Hz that could come from the
potentiometer mounted on the door. Along with RefCmd Pot Min (41) this parameter is used in
determining the slope for interpolating the speed command coming from the potentiometer.

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals