Parameter Descriptions 2-149
7000-TD002A-EN-P – September 2007
Analog Rectifier Test Point 4 [Anlg RecTstPt4]
Linear Number: 125
Default Value: 700
Minimum Value: 0
Maximum Value: 779
Access Level: Service
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog test point 4
(DAC_TP4) on the rectifier side Drive Processor Module (DPM). This is a non-isolated 0-10 V output.
Analog Inverter Test Point 1 [Anlg InvTstPt1]
Linear Number: 511
Default Value: 490
Minimum Value: 0
Maximum Value: 779
Access Level: Service
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog test point ITP1 on
the Drive Processor Module (DPM). This is a non-isolated 0-10 V output.
Analog Inverter Test Point 2 [Anlg InvTstPt2]
Linear Number: 512
Default Value: 289
Minimum Value: 0
Maximum Value: 779
Access Level: Service
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog test point ITP2 on
the Drive Processor Module (DPM). This is a non-isolated 0-10 V output.
Analog Inverter Test Point 3 [Anlg InvTstPt3]
Linear Number: 126
Default Value: 291
Minimum Value: 0
Maximum Value: 779
Access Level: Service
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog test point 3
(DAC_TP3) on the inverter side Drive Processor Module (DPM). This is a non-isolated 0-10 V output.
Analog Inverter Test Point 4 [Anlg InvTstPt4]
Linear Number: 127
Default Value: 306
Minimum Value: 0
Maximum Value: 779
Access Level: Service
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog test point 4
(DAC_TP4) on the inverter side Drive Processor Module (DPM). This is a non-isolated 0-10 V output.

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals