Parameter Descriptions 2-131
7000-TD002A-EN-P – September 2007
Reference Command Mask [Ref Cmd Mask]
Linear Number: 248
Default Value: 11111111
Access Level: Basic
Read/Write: Read/Write
This parameter specifies which adapters can issue the reference command. A one represents the
adapter that can issue the reference command, a zero represents an adapter that cannot issue the
reference command. There are 8 adapters available, from Adapter0 to Adapter7.
Bit Enum Text Description
0 Adapter 0 Host
1 Adapter 1
2 Adapter 2
3 Adapter 3 (Currently unused)
4 Adapter 4 (Currently unused)
5 Adapter 5
6 Adapter 6 (Currently unused)
7 Adapter 7 Programming Terminal
Fault Reset Command Mask [Reset Mask]
Linear Number: 247
Default Value: 11111111
Access Level: Basic
Read/Write: Read/Write
This parameter specifies which adapters can issue the reset command. A one represents the adapter
that can issue the reset command, a zero represents an adapter that cannot issue the reset command.
There are 8 adapters available, from Adapter0 to Adapter7.
Bit Enum Text Description
0 Adapter 0 Host
1 Adapter 1
2 Adapter 2
3 Adapter 3 (Currently unused)
4 Adapter 4 (Currently unused)
5 Adapter 5
6 Adapter 6 (Currently unused)
7 Adapter 7 (Currently unused)

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals