Parameter Descriptions 2-59
7000-TD002A-EN-P – September 2007
Preset Jog Speed [Preset Jog Speed]
Linear Number: 40
Default Value: 6.0 Hz
Minimum Value: 1.0 Hz
Maximum Value: 60.0 Hz
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the preset jog speed command, which is selected by the parameter Speed Ref
Select (7).
Preset Speed 1 [Preset Speed 1]
Linear Number: 33
Default Value: 30.0 Hz
Minimum Value: 0.5 Hz
Maximum Value: 75.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the preset speed 1 command which is selected by the parameter Speed Ref
Select (7).
Preset Speed 2 [Preset Speed 2]
Linear Number: 34
Default Value: 35.0 Hz
Minimum Value: 0.5 Hz
Maximum Value: 75.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the preset speed 2 command which is selected by the parameter Speed Ref
Select (7).
Preset Speed 3 [Preset Speed 3]
Linear Number: 35
Default Value: 40.0 Hz
Minimum Value: 0.5 Hz
Maximum Value: 75.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the preset speed 3 command which is selected by the parameter Speed Ref
Select (7).

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals