2-96 Parameter Descriptions
7000-TD002A-EN-P – September 2007
Parallel Drive Warning Mask [PD Wrn Mask]
Linear Number: 759
Default Value: 1111111111111111
Access Level: Service
Read/Write: Read/Write
These are the parallel drive warning Mask.
Bit Enum Text Description
0 Hub Comm Wrn Hub (PLC) Communications Loss
1 Duplcte Mstr Duplicate Master-master only
2 Dclnd Mstr Slave Declined Master-slave only
3 Slv RfsdMstr Slave Refused Master-master only
4 InvldMstrReq Invalid Master Request-slave only
5 Xfer Disable Transfer Disabled-master only
6 Unused
7 Unused
8 Slave 0 Comm Slave 0 DAN Communications Loss-master only
9 Slave 1 Comm Slave 1 DAN Communications Loss-master only
10 Slave 2 Comm Slave 2 DAN Communications Loss-master only
11 Slave 3 Comm Slave 3 DAN Communications Loss-master only
12 Slave 4 Comm Slave 4 DAN Communications Loss-master only
13 Slave 5 Comm Slave 5 DAN Communications Loss-master only
14 Slave 6 Comm Slave 6 DAN Communications Loss-master only
15 Slave 7 Comm Slave 7 DAN Communications Loss-master only
Alarms Parameters
Standard XIO Fault [Stnd XIO Fault]
Linear Number: 433
Access Level: Service
Read/Write: Read Only
This parameter specifies those inputs on the standard XIO card, which have been configured as faults
(Class 1 or Class 2). A ‘1’ represents an active fault as follows:
Bit Enum Text Description
0 Input Protn1 Input Protection 1 fault
1 TxReacOvrTmp Isolation Transformer/Line Reactor Overtemperature fault
2 DCLinkOvrTmp DC Link / Common-Mode Choke Overtemperature fault
3 Motor Protn Motor Protection fault
4 Input Protn2 Input Protection 2 fault
5 Aux Protn Auxiliary Protection fault
6 Unused
7 Unused