Parameter Descriptions 2-21
7000-TD002A-EN-P – September 2007
Drive Overload Value [Drive Overload]
Linear Number: 551
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the normalized value of drive overload. A warning is issued when the value is
equal to the parameter Drv OvrLoad Wrn (240) and the drive is tripped when the value reaches 1.0.
Motor Overload Value [Motor Overload]
Linear Number: 550
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the normalized value of motor overload. A warning is issued when the value is
equal to the parameter Mtr OvrLoad Wrn (351) and the drive is tripped when the value reaches 1.0.
Neutral Resistor Overload Value [RNeutral OvrLoad]
Linear Number: 682
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the normalized value of the Neutral Resistor overload, and is active only for
Direct-to-Drive PF7000 drives. The drive is faulted when the value reaches 1.0.
Bypass Voltage Unbalance Value [Bypass VoltUnbal]
Linear Number: 428
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the value of voltage unbalance between the 3 phases on the top of the bypass
contactor for Synchronous Transfer applications. A fault is issued when the value exceeds the parameter
LineVoltUnbalTrp (271) for the duration set in LineVoltUnbalDly (272).
Master Voltage Unbalance Value [Master VoltUnbal]
Linear Number: 610
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the value of voltage unbalance between the 3 phases on the master rectifier
bridge. A fault is issued when the value exceeds the parameter LineVoltUnbalTrp (271) for the duration
set in LineVoltUnbalDly (272).

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals