Parameter Descriptions 2-23
7000-TD002A-EN-P – September 2007
Motor Current Unbalance Value [Motor Cur Unbal]
Linear Number: 263
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the value of current unbalance between the 3 phases on the drive output
measured at the LEMs. A fault is issued when the value exceeds the parameter Mtr CurUnbal Trp (208)
for the duration set in Mtr CurUnbal Trp (214).
Motor Flux Unbalance Value [Motor Flux Unbal]
Linear Number: 619
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the value of flux unbalance between the 3 phases on the drive output, measured
with the voltage sensing board. A fault is issued when the value exceeds the parameter Mtr FluxUnbal
Trp (585) for the duration set in Mtr FluxUnbal Trp (586).
Fault Output [Fault Output]
Linear Number: 490
Minimum Value: 0
Maximum Value: 1
Access Level: Service
Read/Write: Read Only
This parameter is used for troubleshooting and allows the user to properly use a chart recorder,
oscilloscope or a similar device to trigger on a drive fault and capture useful test point data. The
parameter goes from 0 to the maximum value of 1 whenever any fault occurs. Assigning this parameter
to any one of the test points on the DPM or 0-10V outputs on the Analog Control Board, an output that will
change state from 0V to 10V on a fault will be produced. This output can be used as a trigger for
capturing other drive data from test points during a fault.
Warning Output [Warning Output]
Linear Number: 700
Minimum Value: 0
Maximum Value: 1
Access Level: Service
Read/Write: Read Only
This parameter is used for troubleshooting and allows the user to properly use a chart recorder,
oscilloscope or a similar device to trigger on a drive fault and capture useful test point data. The
parameter goes from 0 to the maximum value of 1 whenever any warning occurs. Assigning this
parameter to any one of the test points on the DPM or 0-10V outputs on the Analog Control Board, an
output that will change state from 0V to 10V on a warning will be produced. This output can be used as a
trigger for capturing other drive data from test points during a warning condition.
Scope Trigger [Scope Trigger]
Linear Number: 689
Minimum Value: 0
Maximum Value: 1
Access Level: Service
Read/Write: Read Only
This parameter is set high when the Trending is triggered. The parameter can be assigned to a Test
Point in order to trigger a scope.

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals