2-22 Parameter Descriptions
7000-TD002A-EN-P – September 2007
Slave 1 Voltage Unbalance Value [Slave1 VoltUnbal]
Linear Number: 611
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the value of voltage unbalance between the 3 phases on the slave 1 bridge
(18pulse drives only). A fault is issued when the value exceeds the parameter LineVoltUnbalTrp (271) for
the duration set in LineVoltUnbalDly (272).
Slave 2 Voltage Unbalance Value [Slave2 VoltUnbal]
Linear Number: 612
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the value of voltage unbalance between the 3 phases on the slave 2 bridge
(18pulse drives only). A fault is issued when the value exceeds the parameter LineVoltUnbalTrp (271) for
the duration set in LineVoltUnbalDly (272).
Master Current Unbalance Value [Master Cur Unbal]
Linear Number: 613
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the value of current unbalance between the 3 phases on the master bridge. A
fault is issued when the value exceeds the parameter Line CurUnbalTrp (108) for the duration set in Line
CurUnbalDly (109).
Slave 1 Current Unbalance Value [Slave1 Cur Unbal]
Linear Number: 614
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the value of current unbalance between the 3 phases on the slave 1 bridge
(18pulse drives only). A fault is issued when the value exceeds the parameter Line CurUnbalTrp (108) for
the duration set in Line CurUnbalDly (109).
Slave 2 Current Unbalance Value [Slave2 Cur Unbal]
Linear Number: 615
Minimum Value: 0.00
Maximum Value: 1.00
Access Level: Service
Read/Write: Read Only
This parameter specifies the value of current unbalance between the 3 phases on the slave 2 bridge
(18pulse drives only). A fault is issued when the value exceeds the parameter Line CurUnbalTrp (108) for
the duration set in Line CurUnbalDly (109).

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals