Parameter Descriptions 2-67
7000-TD002A-EN-P – September 2007
Skip Speed Band 3 [Skip Speed Band3]
Linear Number: 55
Default Value: 0.0 Hz
Minimum Value: 0.0 Hz
Maximum Value: 5.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the width of skip speed zone 3.
Skip Speed 1 [Skip Speed 1]
Linear Number: 49
Default Value: 90.0 Hz
Minimum Value: 1.0 Hz
Maximum Value: 90.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the center of skip speed zone 1 and is used to avoid mechanical resonances at
certain speeds.
Skip Speed 2 [Skip Speed 2]
Linear Number: 50
Default Value: 90.0 Hz
Minimum Value: 1.0 Hz
Maximum Value: 90.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the center of skip speed zone 2 and is used to avoid mechanical resonances at
certain speeds.
Skip Speed 3 [Skip Speed 3]
Linear Number: 51
Default Value: 90.0 Hz
Minimum Value: 1.0 Hz
Maximum Value: 90.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the center of skip speed zone 3 and is used to avoid mechanical resonances at
certain speeds.
Ramp Test Step [Ramp Test Step]
Linear Number: 80
Default Value: 0.0 Hz
Minimum Value: 0.0 Hz
Maximum Value: 30.0 Hz
Access Level: Service
Read/Write: Read/Write
This parameter specifies the magnitude of the step that is added to the speed command to demonstrate
the response of the speed ramp. If this parameter is set to a non-zero value, the drive will continuously
ramp up and down between a maximum speed equal to the speed command plus the value of this
parameter, and a minimum value equal to the speed command minus the value of this parameter. The
ramp test function is intended for use in factory test only. This parameter is not saved and is initialized to
zero at power up.