2-64 Parameter Descriptions
7000-TD002A-EN-P – September 2007
Deceleration Time 1 [Decel Time 1]
Linear Number: 69
Default Value: 5.0 sec
Minimum Value: 0.0 sec
Maximum Value: 1200.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time for the speed reference to decrease from Ramp Speed 1 to zero.
Deceleration Time 2 [Decel Time 2]
Linear Number: 70
Default Value: 3.0 sec
Minimum Value: 0.0 sec
Maximum Value: 1200.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time for the speed reference to decrease from Ramp Speed 2 to Ramp
Speed 1.
Deceleration Time 3 [Decel Time 3]
Linear Number: 71
Default Value: 14.0 sec
Minimum Value: 0.0 sec
Maximum Value: 1200.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time for the speed reference to decrease from Ramp Speed 3 to Ramp
Speed 2.
Deceleration Time 4 [Decel Time 4]
Linear Number: 72
Default Value: 10.0 sec
Minimum Value: 0.0 sec
Maximum Value: 1200.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time for the speed reference to decrease from Ramp Speed 4 to Ramp
Speed 3.
Ramp Speed 1 [Ramp Speed 1]
Linear Number: 73
Default Value: 5.0 Hz
Minimum Value: 5.0 Hz
Maximum Value: 100.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the first break point in the speed ramp. In conjunction with Accel Time 1 (65), it
is used to determine the rate at which the drive will ramp the output stator frequency during flying starts.
For details refer to section of flying re-start in Chapter 1 – Functional Description.