2-24 Parameter Descriptions
7000-TD002A-EN-P – September 2007
Parameter Error [Parameter Error]
Linear Number: 597
Minimum Value: 0
Maximum Value: 65535
Access Level: Basic
Read/Write: Read Only
This parameter specifies the linear number of the parameter in the database having a value that’s out of
range. Only one parameter linear number can be specified at a time in the parameter error. This means
that more than one parameter can have an error but only one of them is specified.
Feature Select Parameters
Operating Mode [Operating Mode]
Linear Number: 4
Default Value: Normal
Access Level: Monitor
Read/Write: Read/Write when Stopped
This parameter specifies the operating modes of the drive. It is not saved and is set to Normal at power
up. This parameter cannot be changed when the drive is running. Refer to the Chapter 1 – Functional
Description in the PowerFlex 7000 User Manual for detailed description of the test modes.
The possible operating modes are:
Normal Normal operating mode
Gate Test Gate Test mode (medium voltage off)
DC Current DC Current test mode
System Test System Test mode (medium voltage off)
Open Circuit Open Circuit test mode (needs output contactor or disconnected motor)
Open Loop Open Loop test mode (for induction motors only)