Parameter Descriptions 2-35
7000-TD002A-EN-P – September 2007
Line Capacitor Frequency [Line Cap Freq]
Linear Number: 32
Default Value: 60 Hz
Minimum Value: 50 Hz
Maximum Value: 60 Hz
Access Level: Service
Read/Write: Read/Write when Stopped
This parameter specifies the rated nameplate frequency of the line filter capacitors. This parameter only
applies to drives with a PWM rectifier.
Line Capacitor kVAR [Line Cap kVAR]
Linear Number: 15
Default Value: 400 kvar
Minimum Value: 1 kvar
Maximum Value: 7500 kvar
Access Level: Service
Read/Write: Read/Write when Stopped
This parameter specifies the total three-phase nameplate kVAR of the line filter capacitors. This
parameter only applies to drives with a PWM rectifier.
Line Capacitor Voltage [Line Cap Volts]
Linear Number: 16
Default Value: 4160 V
Minimum Value: 100 V
Maximum Value: 10000 V
Access Level: Service
Read/Write: Read/Write when Stopped
This parameter specifies the nameplate voltage rating of the line filter capacitors. This parameter applies
to only drives with a PWM rectifier.
Line Reactor Inductance [Line Reactor]
Linear Number: 624
Default Value: 0.00 mH
Minimum Value: 0.00 mH
Maximum Value: 50.00 mH
Access Level: Service
Read/Write: Read/Write when Stopped
This parameter specifies the value of the AC side line reactor in mH. Refer to the nameplate mounted on
the reactor, or to the dimensional drawings.