Parameter Descriptions 2-121
7000-TD002A-EN-P – September 2007
Motor Neutral Over voltage Delay [Mtr NeutVolt Dly]
Linear Number: 190
Default Value: 1.0 sec
Minimum Value: 0.0 sec
Maximum Value: 10.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time the motor neutral to ground voltage must remain above the trip level
before a motor neutral over voltage fault is indicated.
Motor Over speed Trip [Mtr OvrSpeed Trp]
Linear Number: 185
Default Value: 66.0 Hz
Minimum Value: 0.0 Hz
Maximum Value: 120.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the level the motor speed must exceed before a motor over speed fault is
indicated.
Motor Over speed Delay [Mtr OvrSpeed Dly]
Linear Number: 186
Default Value: 0.5 sec
Minimum Value: 0.0 sec
Maximum Value: 2.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time interval for which the motor speed must exceed the trip level before a
motor over speed fault is indicated.
Motor Overload Trip [Mtr OvrLoad Trp]
Linear Number: 179
Default Value: 1.15 pu
Minimum Value: 0.00 pu
Maximum Value: 4.00 pu
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the maximum motor current which will cause the drive to trip on a motor
overload fault after a time interval specified by parameter Mtr OvrLoad Dly (180).
Motor Overload Delay [Mtr OvrLoad Dly]
Linear Number: 180
Default Value: 60.0 sec
Minimum Value: 0.0 sec
Maximum Value: 600.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time the motor will operate at the overload trip level Mtr OvrLoad Trp (179)
before a motor overload fault is indicated.