2-118 Parameter Descriptions
7000-TD002A-EN-P – September 2007
Rectifier Heatsink Temperature Trip [RecHSink TempTrp]
Linear Number: 111
Default Value: 55 C
Minimum Value: 0 C
Maximum Value: 100 C
Access Level: Service
Read/Write: Read/Write
This parameter specifies the level at which the drive will trip on a rectifier heat sink over temperature fault.
Inverter Heatsink Temperature Warning [InvHSink TempWrn]
Linear Number: 316
Default Value: 61 C
Minimum Value: 0 C
Maximum Value: 100 C
Access Level: Service
Read/Write: Read/Write
This parameter specifies the level at which the drive will issue an inverter heat sink over temperature
warning.
Inverter Heatsink Temperature Trip [InvHSink TempTrp]
Linear Number: 315
Default Value: 64 C
Minimum Value: 0 C
Maximum Value: 100 C
Access Level: Service
Read/Write: Read/Write
This parameter specifies the level at which the drive will trip on an inverter heat sink over temperature fault.
Integral Isolation Transformer Air Flow Nominal Value [IsoTx AirFlowNom]
Linear Number: 656
Default Value: 3.6 V
Minimum Value: 0.0 V
Maximum Value: 10.0 V
Access Level: Service
Read/Write: Read/Write
This parameter specifies the nominal (operating) voltage level for the air pressure sensor in the Isolation
Transformer section of the A-Frame drive. This parameter operates with the same functionality as that of
the converter pressure sensor. THIS PARAMETER IS ACTIVE FOR A-FRAME DRIVES ONLY.
Integral Isolation Transformer Air Flow Warning [IsoTx AirFlowWrn]
Linear Number: 655
Default Value: 3.0 V
Minimum Value: 0.0 V
Maximum Value: 10.0 V
Access Level: Service
Read/Write: Read/Write
This parameter specifies the warning level for the air pressure sensor in the Isolation Transformer section
of the A-Frame drive. THIS PARAMETER IS ACTIVE FOR A-FRAME DRIVES ONLY.

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals