2-66 Parameter Descriptions
7000-TD002A-EN-P – September 2007
S Curve Acceleration Time 2 [S Curve Accel 2]
Linear Number: 482
Default Value: 20.0 sec
Minimum Value: 0.0 sec
Maximum Value: 1200.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the total acceleration time when the S-Curve starting profile is selected, and the
acceleration 2 time is chosen through DPI logic command.
S Curve Deceleration Time 1 [S Curve Decel 1]
Linear Number: 479
Default Value: 20.0 sec
Minimum Value: 0.0 sec
Maximum Value: 1200.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the total deceleration time when the S-Curve starting profile is selected, and the
deceleration 1 time is chosen through DPI logic command. This is the default time when S-Curve is
enabled.
S Curve Deceleration Time 2 [S Curve Decel 2]
Linear Number: 480
Default Value: 20.0 sec
Minimum Value: 0.0 sec
Maximum Value: 1200.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the total deceleration time when the S-Curve starting profile is selected, and the
deceleration 2 time is chosen through DPI logic command.
Skip Speed Band 1 [Skip Speed Band1]
Linear Number: 53
Default Value: 0.0 Hz
Minimum Value: 0.0 Hz
Maximum Value: 5.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the width of skip speed zone 1.
Skip Speed Band 2 [Skip Speed Band2]
Linear Number: 54
Default Value: 0.0 Hz
Minimum Value: 0.0 Hz
Maximum Value: 5.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the width of skip speed zone 2.