2-48 Parameter Descriptions
7000-TD002A-EN-P – September 2007
Autotune Isd Step [Autotune Isd Stp]
Linear Number: 216
Default Value: 0.100 pu
Minimum Value: 0.010 pu
Maximum Value: 0.200 pu
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the size of the step that is added to the magnetizing current command during
auto-tuning of the flux regulator for synchronous machines. It is not used for induction motors.
Contact factory for availability
Autotune Speed Command [Autotune Spd Cmd]
Linear Number: 213
Default Value: 30.0 Hz
Minimum Value: 20.0 Hz
Maximum Value: 60.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the speed command used during auto-tuning of the flux regulator and total
inertia. The overall drive Speed Command Minimum and Maximums are still active during auto-tuning.
Autotune Torque Step [Autotune Trq Stp]
Linear Number: 215
Default Value: 0.100 pu
Minimum Value: 0.050 pu
Maximum Value: 0.500 pu
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the size of the torque step that is added to the torque command during auto-
tuning of the total inertia. A value of 1.000 corresponds to rated torque. The overall Torque Command
Limits are still active during auto-tuning.

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals