Parameter Descriptions 2-111
7000-TD002A-EN-P – September 2007
Rectifier Over Voltage Delay [Rec OvrVolt Dly]
Linear Number: 174
Default Value: 10 msec
Minimum Value: 0 msec
Maximum Value: 100 msec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time the Rectifier voltage must remain above the trip level before a Rectifier
over voltage fault is indicated.
Inverter Over voltage Trip [Inv OvrVolt Trp]
Linear Number: 193
Default Value: 1.50 pu
Minimum Value: 0.00 pu
Maximum Value: 2.00 pu
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the level the inverter output voltage must exceed before an inverter over voltage
fault is indicated. The protection scheme has been realized in hardware on ACB.
Inverter Over voltage Delay [Inv OvrVolt Dly]
Linear Number: 194
Default Value: 10 msec
Minimum Value: 0 msec
Maximum Value: 100 msec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time the Inverter voltage must remain above the trip level before an inverter
over voltage fault is indicated.
Line Voltage Unbalance Trip [LineVoltUnbalTrp]
Linear Number: 271
Default Value: 0.05 pu
Minimum Value: 0.00 pu
Maximum Value: 1.00 pu
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the level of the unbalance in the line voltage which will cause a line voltage
unbalance fault to be indicated.
Line Voltage Unbalance Delay [LineVoltUnbalDly]
Linear Number: 272
Default Value: 1.0 sec
Minimum Value: 0.0 sec
Maximum Value: 10.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the time the line voltage unbalance must remain above trip level before a line
voltage unbalance fault is indicated.