2-146 Parameter Descriptions
7000-TD002A-EN-P – September 2007
Analog Output 3 [Anlg Output3]
Linear Number: 515
Default Value: 0
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog port 3 on the Analog
Control Board (ACB). The output is scalable using Anlg Out3 Scale (187). This is a non-isolated 0-10 V
output.
Analog Output 4 [Anlg Output4]
Linear Number: 508
Default Value: 0
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog port 4 on the Analog
Control Board (ACB). The output is scalable using Anlg Out4 Scale (123). This is a non-isolated 0-10 V
output.
Analog 4-20 mA Output [Anlg 4-20mAOut]
Linear Number: 516
Default Value: 337
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog current loop
transmitter on the Analog Control Board (ACB). This is an isolated 4-20 mA (programmable) output. The
default value of 337 corresponds to Rotor Frequency which is the absolute value of the measured motor
speed in Hz given by Speed Feedback (289).
Analog Meter 1 Scale [AnlgMeter1 Scale]
Linear Number: 521
Default Value: 1.00
Minimum Value: 0.00
Maximum Value: 655.35
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the scale to be used for Analog Meter 1 parameter.
Analog Meter 2 Scale [AnlgMeter2 Scale]
Linear Number: 522
Default Value: 1.00
Minimum Value: 0.00
Maximum Value: 655.35
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the scale to be used for Analog Meter 2 parameter.