EasyManuals Logo

Rockwell Automation PowerFlex 7000 Technical Data

Rockwell Automation PowerFlex 7000
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #190 background imageLoading...
Page #190 background image
2-146 Parameter Descriptions
7000-TD002A-EN-P – September 2007
Analog Output 3 [Anlg Output3]
Linear Number: 515
Default Value: 0
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog port 3 on the Analog
Control Board (ACB). The output is scalable using Anlg Out3 Scale (187). This is a non-isolated 0-10 V
output.
Analog Output 4 [Anlg Output4]
Linear Number: 508
Default Value: 0
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog port 4 on the Analog
Control Board (ACB). The output is scalable using Anlg Out4 Scale (123). This is a non-isolated 0-10 V
output.
Analog 4-20 mA Output [Anlg 4-20mAOut]
Linear Number: 516
Default Value: 337
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog current loop
transmitter on the Analog Control Board (ACB). This is an isolated 4-20 mA (programmable) output. The
default value of 337 corresponds to Rotor Frequency which is the absolute value of the measured motor
speed in Hz given by Speed Feedback (289).
Analog Meter 1 Scale [AnlgMeter1 Scale]
Linear Number: 521
Default Value: 1.00
Minimum Value: 0.00
Maximum Value: 655.35
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the scale to be used for Analog Meter 1 parameter.
Analog Meter 2 Scale [AnlgMeter2 Scale]
Linear Number: 522
Default Value: 1.00
Minimum Value: 0.00
Maximum Value: 655.35
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the scale to be used for Analog Meter 2 parameter.

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals