Parameter Descriptions 2-145
7000-TD002A-EN-P – September 2007
Analog Meter 3 [Anlg Meter3]
Linear Number: 519
Default Value: 363
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog meter 3 on the
Analog Control Board (ACB). The meter output is scalable using AnlgMeter3 Scale (523). This is a non-
isolated 0-10 V output. The default value of 363 corresponds to the Motor Speed RPM parameter.
Analog Meter 4 [Anlg Meter4]
Linear Number: 520
Default Value: 364
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog meter 4 on the
Analog Control Board (ACB). The meter output is scalable using AnlgMeter4 Scale (524). This is a non-
isolated 0-10 V output. The default value of 364 corresponds to the Motor Power parameter.
Analog Output 1 [Anlg Output1]
Linear Number: 513
Default Value: 0
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog port 1 on the Analog
Control Board (ACB). The output is scalable using Anlg Out1 Scale (183). This is a non-isolated 0-10 V
output.
Analog Output 2 [Anlg Output2]
Linear Number: 514
Default Value: 0
Minimum Value: 0
Maximum Value: 779
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog port 2 on the Analog
Control Board (ACB). The output is scalable using Anlg Out2 Scale (184). This is a non-isolated 0-10 V
output.