Parameter Descriptions 2-41
7000-TD002A-EN-P – September 2007
Hardware Options 2 [HardwareOptions2]
Linear Number: 274
Default Value: 0000000000000000
Access Level: Service
Read/Write: Read/Write
This parameter allows the user to select additional hardware options. The options available are:
Bit Enum Text Description
0 Intgrl IsoTx Integral Isolation Transformer installed in the drive
1 Unused
2 Unused
3 Unused
4 Unused
5 Unused
6 Unused
7 Unused
8 Unused
9 Unused
10 Unused
11 Unused
12 Unused
13 Unused
14 Unused
15 Unused
Number of Power Supplies [Number PwrSup]
Linear Number: 575
Default Value: 1
Minimum Value: 1
Maximum Value: 4
Access Level: Service
Read/Write: Read/Write when Stopped
This parameter specifies the total number of AC/DC power supplies installed in the drive. This number
includes the redundant power supply (if installed). In a multi power supply system there can only be one
redundant power supply.
Motor Ratings Parameters
Rated Motor Current [Rated Motor Amps]
Linear Number: 23
Default Value: 159 A
Minimum Value: 10 A
Maximum Value: 1500 A
Access Level: Basic
Read/Write: Read/Write when Stopped
This parameter specifies the rated full load current of the motor. This parameter is internally scaled and
used as the base value in all the drive per-unit calculations.