2-148 Parameter Descriptions
7000-TD002A-EN-P – September 2007
Analog Output 4 Scale [Anlg Out4 Scale]
Linear Number: 123
Default Value: 1.00
Minimum Value: 0.00
Maximum Value: 655.35
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the scale to be used for ACB Port 3 parameter.
Analog 4-20 mA Current Scale [Anlg4-20mA Scale]
Linear Number: 188
Default Value: 2.00
Minimum Value: 0.00
Maximum Value: 655.35
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the scale to be used for Analog 4-20mA Current Loop parameter.
Analog Rectifier Test Point 1 [Anlg RecTstPt1]
Linear Number: 509
Default Value: 321
Minimum Value: 0
Maximum Value: 779
Access Level: Service
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog test point RTP1 on
the Drive Processor Module (DPM). This is a non-isolated 0-10 V output.
Analog Rectifier Test Point 2 [Anlg RecTstPt2]
Linear Number: 510
Default Value: 322
Minimum Value: 0
Maximum Value: 779
Access Level: Service
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog test point RTP2 on
the Drive Processor Module (DPM). This is a non-isolated 0-10 V output.
Analog Rectifier Test Point 3 [Anlg RecTstPt3]
Linear Number: 124
Default Value: 326
Minimum Value: 0
Maximum Value: 779
Access Level: Service
Read/Write: Read/Write
This parameter specifies the linear number of the parameter associated with analog test point 3
(DAC_TP3) on the rectifier side Drive Processor Module (DPM). This is a non-isolated 0-10 V output.