Parameter Descriptions 2-115
7000-TD002A-EN-P – September 2007
Neutral Resistor Overload Trip [RNeut OvrLoadTrp]
Linear Number: 774
Default Value: 5.00
Minimum Value: 0.00
Maximum Value: 655.35
Access Level: Service
Read/Write: Read/Write
This specifies neutral resistor over load trip level. Exceeding this level will trigger a Neutral Resistor over
load fault.
NOTE: Do not change from the default values without consulting the MV Technical Support.
Neutral Resistor Overload Delay [RNeut OvrLoadDly]
Linear Number: 775
Default Value: 2.50 sec
Minimum Value: 0.00 sec
Maximum Value: 655.35 sec
Access Level: Service
Read/Write: Read/Write
This specifies the interval during which the Neutral resistor current stays above the trip level before
triggering an Over load fault.
NOTE: Do not change from the default values without consulting the MV Technical Support.
Neutral Resistor Over Current Trip [RNeut OvrCurTrp]
Linear Number: 776
Default Value: 10.00
Minimum Value: 0.00
Maximum Value: 655.35
Access Level: Service
Read/Write: Read/Write
This specifies the neutral resistor current trip level above which the drive will trigger an over current fault.
NOTE: Do not change from the default values without consulting the MV Technical Support.
R Neutral Over Current Trip Delay [RNeut OvrCurDly]
Linear Number: 777
Default Value: 0.010 sec
Minimum Value: 0.000 sec
Maximum Value: 65.535 sec
Access Level: Service
Read/Write: Read/Write
his specifies the time interval during which the Neutral resistor current stays above the trip to trigger an
over current fault.