Parameter Descriptions 2-65
7000-TD002A-EN-P – September 2007
Ramp Speed 2 [Ramp Speed 2]
Linear Number: 74
Default Value: 12.0 Hz
Minimum Value: 5.0 Hz
Maximum Value: 100.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the second break point in the speed ramp. It must be greater than Ramp Speed 1.
Ramp Speed 3 [Ramp Speed 3]
Linear Number: 75
Default Value: 54.0 Hz
Minimum Value: 5.0 Hz
Maximum Value: 100.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the third break point in the speed ramp. It must be greater than Ramp Speed 2.
Ramp Speed 4 [Ramp Speed 4]
Linear Number: 76
Default Value: 60.0 Hz
Minimum Value: 5.0 Hz
Maximum Value: 100.0 Hz
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the fourth break point in the speed ramp. It must be greater than Ramp Speed 3.
S Curve Percent [S Curve Percent]
Linear Number: 475
Default Value: 0 %
Minimum Value: 0 %
Maximum Value: 100 %
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the non-linear part of the S-curve acceleration profile expressed as percentage
of the total S-curve profile. Set this parameter to 0% to disable S-curve Profile and allow Ramp Profile to
be the active profile.
S Curve Acceleration Time 1 [S Curve Accel 1]
Linear Number: 481
Default Value: 20.0 sec
Minimum Value: 0.0 sec
Maximum Value: 1200.0 sec
Access Level: Advanced
Read/Write: Read/Write
This parameter specifies the total acceleration time when the S-Curve starting profile is selected, and the
acceleration 1 time is chosen through DPI logic command. This is the default time when S-Curve is
enabled.