2-208 Parameters Listed by Group
7000-TD002A-EN-P – September 2007
Torque Control Parameters
Name Min. Max. Default Units
Read-
Only
Access
291 Torque Reference -4.000 4.000 - Y Advanced
147 Active Trq Limit -4.000 4.000 - Y Advanced
86 TrqCmd0 SensrLss 0.00 4.00 0.40 N Advanced
87 TrqCmd1 SensrLss 0.00 4.00 0.40 N Advanced
91 Trq Cmd External -4.000 4.000 0.000 N Advanced
90 Trq Control Mode - - Speed Reg N Advanced
84 Trq Lmt Motoring 0.00 4.00 1.05 N Advanced
85 Trq Lmt Braking 0.00 4.00 0.50 N Advanced
658 Trq Lmt Overload 0.00 4.00 1.00 N Advanced
747 Pwr Lmt Motoring 0.00 4.00 1.50 N Advanced
748 Pwr Lmt Braking 0.00 4.00 1.50 N Advanced
641 TrqCmd0 Tach 0.00 4.00 0.00 N Service
Flux Control Parameters
Name Min. Max. Default Units
Read-
Only
Access
305 Flux Reference 0.000 2.000 - pu Y Advanced
306 Flux Feedback 0.000 2.000 - pu Y Advanced
307 Flux Error -2.000 2.000 - pu Y Advanced
310 Mtr Flux CurCmd -2.000 2.000 - pu Y Advanced
308 FluxCur Feedfwd -2.000 2.000 - pu Y Advanced
309 FluxCurRegulator -2.000 2.000 - pu Y Advanced
312 Inv Flux CurCmd -2.000 2.000 - pu Y Advanced
328 Alpha Inverter -360.0 360.0 - deg Y Advanced
314 Field CurCmd 0.000 2.000 - pu Y Advanced
57 Field Current -2.000 2.000 - pu Y Service
623 Flux Cmd Limit 0.000 1.500 - pu Y Service
304 PFC Flux Command -1.500 1.500 - pu Y Service
97 FlxReg Bandwidth 1.0 30.0 10.0 r/s N Advanced
100 FlxCmd RatedLoad 0.000 1.500 0.900 pu N Advanced
103 FlxCmd No Load 0.400 1.500 0.700 pu N Advanced
78 Motor Flux Time 0.0 10.0 3.0 sec N Advanced
107 Icd Command Gain 0.0 1.0 0.5 N Advanced
106 Field Bandwidth 0.1 100.0 10.0 r/s N Advanced
98 Base Speed 25.0 100.0 60.0 Hz N Service
102 Flux RefStep 0.000 0.100 0.000 pu N Service