2-214 Parameters Listed by Group
7000-TD002A-EN-P – September 2007
Analog Inputs Parameters
Name Min. Max. Default Units
Read-
Only
Access
652 Anlg Inp Config - - 0000000000000001 Hex N Service
630 Speed Pot Vmin -10.00 10.00 0.00 V N Service
631 Speed Pot Vmax -10.00 10.00 10.00 V N Service
632 Anlg Inp1 Vmin -10.00 10.00 0.00 V N Service
633 Anlg Inp1 Vmax -10.00 10.00 10.00 V N Service
634 Anlg Inp2 Vmin -10.00 10.00 0.00 V N Service
635 Angl Inp2 Vmax -10.00 10.00 10.00 V N Service
636 Anlg Inp3 Vmin -10.00 10.00 0.00 V N Service
637 Anlg Inp3 Vmax -10.00 10.00 10.00 V N Service
Analog Outputs Parameters
Name Min. Max. Default Units
Read-
Only
Access
517 Anlg Meter1 0 779 361 N Basic
518 Anlg Meter2 0 779 362 N Basic
519 Anlg Meter3 0 779 363 N Basic
520 Anlg Meter4 0 779 364 N Basic
513 Anlg Output1 0 779 0 N Basic
514 Anlg Output2 0 779 0 N Basic
515 Anlg Output3 0 779 0 N Basic
508 Anlg Output4 0 779 0 N Basic
516 Anlg 4-20mAOut 0 779 337 N Basic
521 AnlgMeter1 Scale 0.00 655.35 1.00 N Basic
522 AnlgMeter2 Scale 0.00 655.35 1.00 N Basic
523 AnlgMeter3 Scale 0.00 655.35 1.00 N Basic
524 AnlgMeter4 Scale 0.00 655.35 1.00 N Basic
183 Anlg Out1 Scale 0.00 655.35 1.00 N Basic
184 Anlg Out2 Scale 0.00 655.35 1.00 N Basic
187 Anlg Out3 Scale 0.00 655.35 1.00 N Basic
123 Anlg Out4 Scale 0.00 655.35 1.00 N Basic
188 Anlg4-20mA Scale 0.00 655.35 2.00 N Basic
509 Anlg RecTstPt1 0 779 321 N Service
510 Anlg RecTstPt2 0 779 322 N Service
124 Anlg RecTstPt3 0 779 326 N Service
125 Anlg RecTstPt4 0 779 700 N Service
511 Anlg InvTstPt1 0 779 490 N Service
512 Anlg InvTstPt2 0 779 289 N Service
126 Anlg InvTstPt3 0 779 291 N Service
127 Anlg InvTstPt4 0 779 306 N Service