EasyManuals Logo

Rockwell Automation PowerFlex 7000 Technical Data

Rockwell Automation PowerFlex 7000
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #341 background imageLoading...
Page #341 background image
Troubleshooting 3-53
7000-TD002A-EN-P – September 2007
WARNING
MESSAGE
WARNING
CODE
DESCRIPTION RECOMMENDED ACTIONS
TempFeedbackLoss
(C-Frame Only)
42 While Running, the drive has detected a
missing temperature feedback. A missing
sensor can be interpreted as either 0°C or
over 100°C, and both are unrealistic values.
Verify sensor is completely seated
properly on TFB.
Measure sensor resistance. Replace if
necessary.
NOTE: This is a warning because the
drive should not fault on the loss of the
signal while running. There is no
imminent danger to the drive, but the
user needs to be aware that there is a
temperature feedback signal missing.
Tuning Abort 58 Autotuning could not be completed in 2
minutes or had to be aborted due to drive
stop/fault. Check Alarm queue and perform
manual tuning if problem persists.
Investigate why the Autotune Test
aborted, and Retry Autotune Test
Verify Autotune default parameters are
sufficient to complete test
Make sure the Speed min/max and
ramptime are set to default.
Also Refer ther tuning section in user
manual.
Attempt Manual Tuning
UPS Battery Low 115 Warning that the UPS Battery is low.
This is not very useful as the UPS
battery low occurs at the point where the
UPS can no longer run and a fault is
initiated.
UPS Failed 116 The UPS has had an internal failure.
This is a warning because we do not want a
signal/wiring error to fault the drive. We are
relying on the subsequent power supply
faults to protect the drive.
Investigate the cause for the UPS failure
Check batteries
Verify input voltage/UPS wiring
Refer to UPS manual
Replace UPS if required
UPS on Battery 114 There has been a loss of control power
feeding the UPS and it has switched to its
internal battery pack.
Check for the reason that the UPS was
required, and rectify the situation before
the battery power expires
UPS on Bypass 113 Warning that the UPS is now on Bypass.
This occurs when the drive has switched to
UPS, but a UPS fault has forced the system
to switch to Bypass, if available.
Investigate cause for initial transfer to
UPS, and correct.
Then investigate why the UPS failed and
was forced to go to bypass
Xfer Disabled 125 Transfer Disabled-master only.
This warning is for parallel drives only and
indicates that the transfer of mastership has
been disabled because they are performing
certain functions e.g Synchronous transfer
or stopping during a Class 2 fault.
Transfer of master not allowed while
drive is stopping

Table of Contents

Other manuals for Rockwell Automation PowerFlex 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 7000 and is the answer not in the manual?

Rockwell Automation PowerFlex 7000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 7000
CategoryDC Drives
LanguageEnglish

Related product manuals