EasyManua.ls Logo

YASKAWA AC Drive-A1000 - Page 423

YASKAWA AC Drive-A1000
534 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name Description Values Page
H3-14
(41C)
Analog Input Terminal
Enable Selection
All Modes
Determines which analog input terminals will be enabled when a digital input
programmed for “Analog input enable” (H1-oo = C) is activated.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
Default: 7
Range: 1 to 7
231
OLV/PMOLV/PM AOLV/PMAOLV/PM CLV/PMCLV/PM
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
H3 Multi-Function Analog Input Settings
H3-oo
Setting
Function Description Page
0 Frequency bias
All Modes
10 V = E1-04 (maximum output frequency)
231
1 Frequency gain
All Modes
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of -100
to 0%.
231
2
Auxiliary frequency reference 1
(used as a Multi-Step Speed 2)
All Modes
10 V = E1-04 (maximum output frequency)
232
3
Auxiliary frequency reference 2
(3rd step analog)
All Modes
10 V = E1-04 (maximum output frequency)
232
4 Output voltage bias
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG
10 V = E1-05 (motor rated voltage)
232
5 Accel/decel time gain
All Modes
10 V = 100%
232
6 DC Injection Braking current
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG OLV
10 V = Drive rated current
232
7
Overtorque/undertorque
detection level
All Modes
10 V = Drive rated current (V/f, V/f w PG, OLV/PM)
10 V = Motor rated torque (OLV, CLV, AOLV/PM, CLV/PM)
232
8 Stall Prevention level during run
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG
10 V = Drive rated current
232
9 Output frequency lower limit level
All Modes
10 V = E1-04 (maximum output frequency)
233
B PID feedback
All Modes
10 V = 100%
233
C PID setpoint
All Modes
10 V = 100%
233
D Frequency bias
All Modes
10 V = E1-04 (maximum output frequency)
233
E Motor temperature (PTC input)
All Modes
10 V = 100%
233
F Through mode
All Modes
Set this value when using the terminal in the pass-through mode.
233
B.9 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual