EasyManua.ls Logo

YASKAWA V1000 Series

YASKAWA V1000 Series
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
124 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
4.4 Basic Parameter Adjustments
4.4 Basic Parameter Adjustments
This section explains the basic settings required for initial drive operation.
Checking these basic parameter settings during start-up will help to ensure a
successful drive start-up.
If more information is required for parameters not listed in this section, refer to
Parameter List on page 331 as required for a complete listing of drive parameters.
Control Mode Selection
Available Control Modes
Three motor control modes are available. Select the control mode that best suits the
application in which the drive will be used.
Initialize Parameter Values: A1-03
Parameter A1-03 (Initialize Parameters) resets all parameters to the original default
values.
Note: Be sure to save all changed parameter settings by setting o2-03=”1” before
initializing the drive. Your settings will be lost if a 2-wire or 3-wire initialization
using 2220, or 3330 if performed without first saving user parameters. Refer to
Back-up of Parameter Values: o2-03 on page 173.
Control Mode Parameter Main Applications
V/f Control
A1-02 = 0
(default)
General variable speed applications, particularly useful for
running multiple motors from a single drive
When replacing a drive in which parameter settings are
unknown.
Open Loop Vector Control A1-02 = 2
General variable speed applications
Applications requiring high precision, high speed control.
PM Open Loop Vector Control A1-02 = 5
Variable torque applications employing permanent magnet motors
and energy savings.

Table of Contents

Other manuals for YASKAWA V1000 Series

Related product manuals