4.4 Basic Parameter Adjustments
136 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
WARNING! Sudden Movement Hazard. When using the 3-wire run/stop sequence, properly
set the digital input terminal parameter before closing the wiring for the control circuit.
Improper sequencing of run/stop circuitry could result in death or serious injury from moving
equipment.
WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring
the control terminals and ensure parameter b1-17 is set to 0 (drive does not accept a run
command at power up (default)). If the drive is wired for 3-Wire sequence but set up for 2-Wire
sequence (default) and if parameter b1-17 is set to 1 (drive accepts a Run command at power
up), the motor will rotate in reverse direction at power up of the drive and may cause injury.
Note: For safety reasons the drive is default set up not to accept a Run command at power
up (b1-17 = “0”). If a Run command is issued at power up, the Run LED will flash
quickly. Change parameter b1-17 to 1, if this Run command shall be executed by the
drive.
Note: 1. Refer to Parameter List on page 331 for a list of digital input functions.
2. After performing a 3-wire initialization (A1-03 = “3”), the drive will automatically assign
the forward/reverse command to terminal S5.
Stopping Method Selection: b1-03
When a Stop command is issued, the drive stops the motor using one of four
possible methods.
Ramp to Stop (b1-03 = 0)
When b1-03 = 0, the motor will decelerate to a stop when a stop command is
entered. The deceleration time is the time to ramp down from maximum frequency
(E1-04) to zero frequency. The time set in C1-02 will be used except in cases where
an alternate decel time is selected by use of parameter C1-11. Refer to
Acceleration/Deceleration C1-01 to C1-11 on page 141 for information on
deceleration time.
When the output frequency falls below the DC Injection braking start frequency
(b2-01) during deceleration, the DC Injection braking current (b2-02) will be
activated for the specified DC Injection time at stop (b2-04).
This feature can be used to aid in stopping loads where there are low frictional
losses. Refer to Figure 4.17 for further details.

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled

Related product manuals