B.2 Parameter Table
368 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
◆ H Parameters: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
F6 and F7: Serial Communications Option Card Settings
Use F6 parameters to program the drive for serial communication.
F6-01
thru
F6-41
Range reserved −−−AAA
3A2H
to
3D6H
—
F7-01
thru
F7-21
Range reserved −−−AAA
3E5H
to
3F9H
—
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for
A1-02 = 2-OLV control.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
H1: Multi-Function Digital Input
Use H1 parameters to assign functions to the multi-function input terminals.
Unused terminals should be set to "F".
H1-01
Multi-Function Digital Input Terminal
S1 Function Selection
Selects the function of
terminals S1 to S7
Refer to “Multi-Function
Digital Input Selection
Table” for a description of
setting values.
1 to 9F 40 A A A 438 —
H1-02
Multi-Function Digital Input Terminal
S2 Function Selection
1 to 9F 41 A A A 439 —
H1-03
Multi-Function Digital Input Terminal
S3 Function Selection
0 to 9F 24 A A A 400 —
H1-04
Multi-Function Digital Input Terminal
S4 Function Selection
0 to 9F 14 A A A 401 —
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M