4.4 Basic Parameter Adjustments
142 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Program two of the parameters H1-xx to “07” and “7A”. The combination of these
two inputs activates the acceleration/deceleration times as shown below. As the
contacts of the terminals open and close, the following acceleration and
deceleration time combinations are possible:
Automatically Switching Acceleration/Deceleration Times
The drive can automatically switch between acceleration and deceleration times.
When the output frequency reaches the value set to C1-11, the drive will switch
acceleration and deceleration times as shown in the graph below. Setting C1-11 to
0.0 Hz disables this function.
Figure 4. 21
Figure 4.21 Accel/Decel Time Switching Frequency
Accel/Decel Time 1
H1- = 7
Accel/Decel Time 2
H1- = 1A
Acceleration Time Deceleration Time
Open (not selected) Open (not selected) C1-01 C1-02
Closed Open (not selected) C1-03 C1-04
Open (not selected) Closed C1-05 C1-06
Closed Closed C1-07 C1-08
Output Frequency
C1-11
ccel/Decel Time
Switch Frequency
C1-07
setting
When the output frequency ҈ C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-07, -08)
C1-01
setting
C1-02
setting
C1-08
setting

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled