EasyManua.ls Logo

YASKAWA V1000 Series

YASKAWA V1000 Series
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.4 Basic Parameter Adjustments
142 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Program two of the parameters H1-xx to “07” and “7A”. The combination of these
two inputs activates the acceleration/deceleration times as shown below. As the
contacts of the terminals open and close, the following acceleration and
deceleration time combinations are possible:
Automatically Switching Acceleration/Deceleration Times
The drive can automatically switch between acceleration and deceleration times.
When the output frequency reaches the value set to C1-11, the drive will switch
acceleration and deceleration times as shown in the graph below. Setting C1-11 to
0.0 Hz disables this function.
Figure 4. 21
Figure 4.21 Accel/Decel Time Switching Frequency
Accel/Decel Time 1
H1- = 7
Accel/Decel Time 2
H1- = 1A
Acceleration Time Deceleration Time
Open (not selected) Open (not selected) C1-01 C1-02
Closed Open (not selected) C1-03 C1-04
Open (not selected) Closed C1-05 C1-06
Closed Closed C1-07 C1-08
Output Frequency
C1-11
ccel/Decel Time
Switch Frequency
C1-07
setting
When the output frequency ҈ C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-07, -08)
C1-01
setting
C1-02
setting
C1-08
setting

Table of Contents