5.7 Operator Programming Errors
240 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Cause Possible Solutions
The following contradictory settings have been made at
the same time:
C6-05 is greater than 6
C6-04 is greater than C6-03 (carrier frequency lower limit
is greater than the upper limit)
If C6-05 is less than or equal to 6, the drive will operate at
C6-03.
Correct the parameter settings.
Upper and lower limits between C6-02 and C6-05
contradict each other.
Correct the parameter settings.