474 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 6 Protective Trip and Warning Functions
Table 415 - Analog Module 4 – Channel 02 Trip Level (Parameter 555)
Analog Module 4 – Channel 02 Over Level Warning
The E300 relay indicates an Analog Module 4 – Channel 02 Over Level warning
if:
No warning currently exists
Analog Module 4 – Channel 02 Over Level Warning is enabled
The maxim
um phase current is equal to or greater than the Analog
Modu
le 4 – Channel 02 Warning Level
When the Analog Module 4 – Channel 02 Over Level Warning conditions are
sa
tis
fied, the:
TRIP/WARN LED flashes a yellow 4-long / 12-short blink pattern
Bit 11 in Analog Warning Status (Parameter 14) sets to 1
Bit 1 in Device Status 0 (Parameter 20) sets to 1
Any relay outputs configured as a Warning Alarm close
Default Value 0
Minimum Value -32768
Maximum Value 32767
Parameter Type INT
Size (Bytes) 2
Scaling Factor 1
Units