592 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 10 EtherNet/IP Communication
Press Ye s to add the preconfigured E300 relay to the Ethernet tree and establish
communication between the E300 relay; the ControlLogix controller begins.
The E300 relay’s configuration data is retained and stored in the ControlLogix
controller and in the RSLogix 5000 or Studio 5000 project.
Press No to return to the new module profile and make additional edits.
12. To access the data provided by the E300 relay EtherNet/IP
Communication Module, navigate to the input tags created by the Add-on
Profile.