Configuration
Parameter manual b maXX BM5800
Document No.: 5.16029.03 Baumüller Nürnberg GmbH
118
of 814
3.4
138.32 Peak current derating
Derating of the peak current of the drive is required for special devices (see ZPower unit
from page 61 and parameter Z138.8 bit 6).
138.34 Torque base value
(from FW version 1.14)
Reference value of the standardized torque parameters.
The torque reference value M
base
was specified the maximum, internal motor torque that
would be available due to a torque current of the same amount as the maximum total cur
-
rent Z19.6.
with:
I
s max
"Max. drive current" Z19.6 in A
Flux
nom
Nominal magnetic flux, 100%
Kt Motor Kt factor Z107.44, in Nm/A
Asynchronous motors or synchronous motors in the field weakening range cannot reach
this torque because of the field current which is required.
The parameter is the reference value of the standardized set value Z18.78.
146.1 Asynchronous motor mode
Bit string to select the control mode of an asynchronous motor
M
base
I
s max
Kt
Flux
nom
100
--------------------
 I
s max
Kt==
Bit no. Meaning
7 ... 0 Reserved
8 Build-up of the flux before the transition in drive manager state 4
(
Z108.6):
1: on
0: off
9 Reserved
10 Command start of the Lh-identification
15 ... 11 Reserved