2000X energy Power Supply Chapter 4: Installation and Setup
Instruction Manual Guards and Safety Equipment
011-003-991 EN 4-35
Table 4.9 DIP Switch Settings*
*Refer to Figure 4.15
4.7 Guards and Safety Equipment
4.7.1 Emergency Stop Control
If you use the Emergency Stop button on the Actuator to terminate a weld, twist the button to reset it. (The
welder will not operate until this button is reset.) You must then press Reset at the power supply. If you are
running automation, you can use external reset that is connected to your User I/O board.
Function Options Default Settings Sw Pos
Seek
Seek on power-up - Checks horn frequency upon
power up and stores the value in memory
Off 1
Auto-Seek - checks horn frequency once each
minute, from the time of the last activation of
ultrasonics
On (This default set-
ting renders Auto-
Seek inoperative)
2
Auto-Seek duration - indicates the length of time
the Auto-Seek function is active
On = short
Off = standard
3
Store at end of weld - updates horn frequency
memory at the end of each weld
Off 4
NOT USED 5
Amplitude
Control
DIP 6 must be in the Off position.
Off 6
Start
short - sets ramp time to 10 ms.
7-On
8-On
7 - 8
medium - sets ramp time to 35 ms.
7-Off
8-On
7 - 8
standard - sets ramp time to 80 ms*.
7-On
8-Off
7 - 8
long - sets ramp time to 105 ms.
7-Off
8-Off
7 - 8