DVP-15MC Series Motion Controller Operation Manual
12-16
Meaning How to deal with
is out of the allowed area.
(%QX0.0~%QX127.7,%MX0.0~%
9030 36912 Object type error
Modify the value of the input parameter
ObjType.
9031 36913
The specified function code for
data reading exceeds the allowed
range.
Specify a new function code which is within
the allowed range.
9040 36928
The local buffer for data sending
has no enough space to meet the
specified length of data.
Modify the start address of the local buffer or
specified data length.
9042 36930
The start address of the local
buffer for data sending is out of
the allowed word register area.
(Valid range:
Modify the start address of the local buffer.
9043 36931
The local buffer specified for data
receiving has no enough space to
meet the specified length of data.
Modify the start address of the local buffer or
specified data length.
9045 36933
The start address of the local
buffer specified for data receiving
is out of the allowed word register
area.
(Valid range:
%MW0~%MW32767)
Modify the start address of the local buffer.
9100 37120
Socket instruction parameter
value exceeds the allowed range.
Modify the Socket instruction parameter
values within the allowed range.
9101 37121
Ethernet physical connection is
disconnected.
Check if the network cable connection is
proper.
9102 37122
TCP remote IP address error Modify the setting for the remote IP address.
TCP port error Modify the remote port setting.
9105 37125
An error occurs in the register
addresses for TCP data sending.
Modify register address for sending TCP
data.
9106 37126
TCP/UDP data receiving is in
process.
The last data receiving has not been
completed and thus the new receiving can
9107 37127
TCP receiving register address
error
Modify the register address for receiving
TCP data.
9108 37128
The length of received data
exceeds the set length in TCP
Set the length of received data to the length
which is greater than or equal to the number
of bytes of the first received data.
9109 37129
The length of received data
exceeds the set length in UDP
Set the length of received data to the length
which is greater than or equal to the number
of bytes of the first piece of received data.
910A 37130 UDP remote IP address error Modify the remote IP address setting.
910B 37131 UDP port error
Local port and remote port can not be 0 at
the same time.
910C 37132
An error occurs in the register
addresses for sent UDP data.
Modify the register addresses for sent data.
910D 37133
An error occurs in the register
addresses for received UDP data.
Modify the register addresses for storing the
received data.