Chapter 12 Troubleshooting
12-17
1
ErrorID
Meaning How to deal with
Hex
Decimal
910E 37134 TCP connection timeout
Check if the Socket configuration is proper
or the remote device works normally.
910F 37135
The length of received data
exceeds the set length in TCP
client mode.
Set the length of received data to the length
which is greater than or equal to the number
of bytes of the first piece of received data.
9110 37136
TCP link is declined by the
remote device.
Check if the remote device is normal or retry
the link to the remote device.
9111 37137
TCP/UDP link has not been
enabled.
Make sure that the link has been enabled.
9112 37138
TCP/UDP link has been
triggered.
The link is being built and thus the link
building can not be re-triggered.
9113 37139
TCP/UDP data sending has been
triggered.
The last data sending has not been
completed and thus the sending can not be
re-triggered.
9114 37140 TCP/UDP link has been built.
The link has been built and thus the
repeated trigger can not build a link.
9115 37141 TCP/UDP link is being disabled.
The link is being disabled and thus the link
disabling can not be re-triggered.
9116 37142 TCP/UDP link is not disabled.
The configuration of Socket parameters can
be conducted only when the link is disabled.
9117 37143
The parameter value for the
length of sent TCP/UDP data
exceeds the limit.
Modify the length of sent data within the
allowed range.
9118 37144
The parameter value for the
length of received TCP/UDP data
exceeds the limit.
Modify the length of received data within the
allowed range.
A000 40960 Cam point number error Modify the cam table number.
A001
40961
Tappet point number error
Modify tappet point number.
A008
40968
M code number error
Modify M code number.
A010
40976
Axes group state machine error
Modify the timing for the instruction execution.
A011 40977
The axes group number exceeds
the allowed range.
Modify the axes group number.
A012 40978
The value of the input parameter
TransitionMode is incorrect.
Modify the input value.
A013 40979
The value of the input parameter
TransitionParameter is incorrect.
Modify the input value.
A014 40980
The setting value of BufferMode
does not match that of
TransitionMode.
Modify the input value.
A015 40981
The value of CircMode is
incorrect.
Modify the input value.
A016 40982
The value of PathChoice is
incorrect.
Modify the input value.
A800 43008
The mechanical gear ratio can not
be 0 or a negative number.
Modify the mechanical gear ratio.
A801 43009
The UnitsPerRotation value can
not be 0 or a negative number.
Modify the UnitsPerRotation value.
A802 43010 Axis type error Modify the axis type.
A803 43011
The value of the modulo can not
be a non-positive number.
Modify the value of the modulo.
A808 43016
Ex_Move is executed again when
the instruction execution has not
been completed yet.
Modify the timing of the instruction execution.