EasyManua.ls Logo

GE D90 Plus - Page 478

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
468 D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
AUTOMATION INPUTS AND OUTPUTS CHAPTER 8: AUTOMATION
Events
Range: Enabled, Disabled
Default: Enabled
If this setting is “Enabled,” every change in the contact input state triggers an event in
the event recorder.
Contact input chatter detection
The D90
Plus
has a chatter detection feature. When enabled, the IED monitors the number
of state changes that occur within a set duration. If this value exceeds a set value, then a
trouble condition is declared for the input and the CONTACT INPUT TROUBLE operand asserts.
The input trouble alarm impacts relay functionality as follows:
Automation logic operands — Operand state is blocked
DNP 3.0 communications — Reporting of the input is blocked
IEC 60870-5-104 communications — Reporting of the input is blocked
IEC 61850 GSSE and IEC 61850 GOOSE — Reporting of the input is blocked
Sequence of events recorder — Reporting of the input is blocked
The trouble condition resets if the input undergoes no state changes for a duration equal
to twice the chatter time setting.
Figure 397: Chatter detection example
Select the Settings > Automation > Automation Inputs/Outputs > Contact Inputs >
Chatter Detection menu to access the contact input chatter detection settings.
Figure 398: Contact input chatter detection configuration
The following settings are applied to all available protection and automation contact
inputs.
48 V 33.6 V
125 V 87.5 V
250 V 175 V
Nominal voltage Validation threshold
2))
21
V
&KDWWHU7LPH
,QSXW
YROWDJH
,QSXW
WURXEOH
$&'5

Table of Contents

Other manuals for GE D90 Plus

Related product manuals