CHAPTER 11: METERING METERING FLEXANALOG PARAMETERS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 579
SRC 1 I2 Mag................................................
Metered negative-sequence current magnitude for source 1
SRC 2................................................................
The analog parameters shown above are available for sources
2 and above.
Power metering analog operands
SRC 1 P............................................................
Metered three-phase real power for source 1
SRC 1 Pa.........................................................
Metered phase A real power for source 1
SRC 1 Pb.........................................................
Metered phase B real power for source 1
SRC 1 Pc .........................................................
Metered phase C real power for source 1
SRC 1 Q...........................................................
Metered three-phase reactive power for source 1
SRC 1 Qa ........................................................
Metered phase A reactive power for source 1
SRC 1 Qb ........................................................
Metered phase B reactive power for source 1
SRC 1 Qc.........................................................
Metered phase C reactive power for source 1
SRC 1 S............................................................
Metered three-phase apparent power for source 1
SRC 1 Sa .........................................................
Metered phase A apparent power for source 1
SRC 1 Sb .........................................................
Metered phase B apparent power for source 1
SRC 1 Sc .........................................................
Metered phase C apparent power for source 1
SRC 1 PF .........................................................
Metered three-phase power factor for source 1
SRC 1 PF A .....................................................
Metered phase A power factor for source 1
SRC 1 PF B .....................................................
Metered phase B power factor for source 1
SRC 1 PF C .....................................................
Metered phase C power factor for source 1
SRC 2................................................................
The analog parameters shown above are available for sources
2 and above.
Energy metering analog operands
SRC 1 Pos Watth.........................................
Metered three-phase real power for source 1
SRC 1 Neg Watth .......................................
Metered phase A real power for source 1
SRC 1 Pos Varh............................................
Metered phase B real power for source 1
SRC 1 Neg Varh...........................................
Metered phase C real power for source 1
SRC 2................................................................
The analog parameters shown above are available for sources
2 and above.
Voltage metering analog operands
SRC 1 Vag RMS............................................
Metered RMS phase A to ground voltage for source 1
SRC 1 Vbg RMS............................................
Metered RMS phase B to ground voltage for source 1
SRC 1 Vcg RMS............................................
Metered RMS phase C to ground voltage for source 1
SRC 1 Vag Angle.........................................
Metered phase A to ground voltage angle for source 1
SRC 1 Vag Mag............................................
Metered phase A to ground voltage magnitude for source 1
SRC 1 Vbg Angle.........................................
Metered phase B to ground voltage angle for source 1
SRC 1 Vbg Mag............................................
Metered phase B to ground voltage magnitude for source 1
SRC 1 Vcg Angle .........................................
Metered phase C to ground voltage angle for source 1
SRC 1 Vcg Mag............................................
Metered phase C to ground voltage magnitude for source 1
SRC 1 Vab RMS............................................
Metered RMS phase A to B voltage for source 1
SRC 1 Vbc RMS............................................
Metered RMS phase B to C voltage for source 1
SRC 1 Vca RMS............................................
Metered RMS phase C to A voltage for source 1
SRC 1 Vab Angle.........................................
Metered phase A to B voltage angle for source 1
SRC 1 Vab Mag............................................
Metered phase A to B voltage magnitude for source 1
SRC 1 Vbc Angle .........................................
Metered phase B to C voltage angle for source 1
SRC 1 Vbc Mag............................................
Metered phase B to C voltage magnitude for source 1
SRC 1 Vca Angle .........................................
Metered phase C to A voltage angle for source 1
SRC 1 Vca Mag............................................
Metered phase A to A voltage magnitude for source 1