CHAPTER 12: LOCAL INTERFACE ANNUNCIATOR PANEL
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 587
Figure 513: Metering value properties window
The following parameters are available.
Parameter
Range: any FlexAnalog parameter
Default: Digital Counter 1 Value
This setting selects a FlexAnalog parameter that specifies the metered value to display
in the annunciator alarm.
Units
Range: up to 4 alphanumeric characters
Default: ---
This setting specifies a four-character alphanumeric string that is used in the
annunciator display of the corresponding metered value.
Scale Factor
Range: None, k (kilo), M (Mega), G (Giga)
Default: None
This setting allows the user to specify the scaling factor for the metering units value.
Multiplier
Range: dependent on selected analog value
Default: 1.0
This setting allows the user to specify a multiplier for the metering parameter value. The
range is restricted to correspond to the selected actual value parameter.
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed analog value. It can be
used to provide for leading character spacing of the display value.
Number of Decimals
Range: 1 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed analog value.