EasyManua.ls Logo

GE P24DM - Page 21

GE P24DM
600 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 78: Automatic restart failed- voltage restored after the set time 154
Figure 79: Start inhibition example 1 159
Figure 80: Start inhibition example 2 160
Figure 81: Time between starts 161
Figure 82: 3 phase VTs and Anti-Backspin (remanent phase-phase) VT configuration 162
Figure 83: REF protection for delta connected winding 168
Figure 84: REF protection for star connected winding 168
Figure 85: Three-slope REF bias characteristic 170
Figure 86: High Impedance REF principle 170
Figure 87: High impedance REF connection 171
Figure 88: REF bias characteristic 172
Figure 89: Low Impedance REF Scaling Factor 175
Figure 90: Circuit Breaker Fail logic - three phase start 183
Figure 91: Circuit Breaker Fail logic - single phase start 184
Figure 92: Circuit Breaker Fail Trip and Alarm 184
Figure 93: Undercurrent and Zero Crossing Detection Logic for CB Fail 185
Figure 94: CB Fail SEF Protection Logic 186
Figure 95: CB Fail Non Current Protection Logic 187
Figure 96: Circuit Breaker mapping 188
Figure 97: CB Fail timing 190
Figure 98: Undervoltage - single and three phase tripping mode (single stage) 205
Figure 99: Overvoltage - single and three phase tripping mode (single stage) 208
Figure 100: Residual Overvoltage logic 211
Figure 101: Residual voltage for a solidly earthed system 212
Figure 102: Residual voltage for an impedance earthed system 213
Figure 103: Negative Sequence Overvoltage logic 214
Figure 104: Positive Sequence Undervoltage logic 216
Figure 105: Positive Sequence Overvoltage logic 217
Figure 106: Moving Average undervoltage logic 218
Figure 107: Moving Average overvoltage logic 219
Figure 108: Moving Average zero sequence voltage logic 219
Figure 109: Moving Average positive sequence voltage logic 220
Figure 110: Moving Average negative sequence voltage logic 220
Figure 111: Average Voltage Protection blocking 220
Figure 112: Underfrequency logic (single stage) 225
Figure 113: Overfrequency logic (single stage) 227
Figure 114: Power system segregation based upon frequency measurements 228
Figure 115: Independent rate of change of frequency logic (single stage) 229
Figure 116: Frequency-supervised rate of change of frequency logic (single stage) 232
Figure 117: Frequency supervised rate of change of frequency protection 233
P24xM Table of Figures
P24xM-TM-EN-2.1 xix

Table of Contents

Related product manuals