Input Calibration - Minimum and Maximum Range Values
Release M DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual 179
April 2017
*Range values for thermocouples are based on a cold junction temperature of 32°F (0°C). These values must be
adjusted for the actual cold junction temperature when using the ambient temperature method for calibrating
thermocouple inputs.
**Resistor network 30755232-002 must be installed in inputs #1 and #2 when using this range, see set up diagram
for details.