ECC800 Data Center Controller
User Manual (for ECC800-Pro)
3 Device Description
Copyright © Huawei Technologies Co., Ltd.
47
Indicat
or
Color
Name
Status
Description
short intervals
skylight actuator fails to register
with the ECC800-Pro (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s (blinking
at 10 Hz, on for 0.05s and then
off for 0.05s) and then turns off
for 0.5s. The cycle lasts for 10s.
ALM
Red
Alarm
indicator
Steady on
A system failure alarm is
generated.
Off
No system alarm is generated.
RF_Z
Green
Communicatio
n status
indicator
Steady on
No network parameters exist, or a
network is to be created.
Blinking at
long intervals
A network is set up, and no node
access is allowed (the indicator
blinks at 0.5 Hz, on for 1sand
then off for 1s).
Blinking at
super short
intervals
A network is set up, and node
access is allowed (the indicator
blinks at 10 Hz, on for 0.05s and
then off for 0.05s).
Blinking
intermittently
at super short
intervals
The skylight actuator is searching
for a network (the indicator
blinks at super short intervals for
0.5s and then turns off for 0.5s).
Communications Ports
The skylight actuator provides one DO port (LOCK/GND) and one DI port (BUTTON/GND).
Table 3-43 lists the LOCK/GND/BUTTON/GND port pin definitions.
Table 3-43 LOCK/GND/BUTTON/GND port pin definitions
Item
Description
LOCK/GND
pin sequence
LOCK
12V_OUT
GND
GND
BUTTON/GN
D pin
sequence
BUTTON
DI3
GND
GND