FusionModule2000 Smart Modular Data Center 
Installation Guide 
2 Installation Preparations 
 
Huawei Proprietary and Confidential                                     
Copyright © Huawei Technologies Co., Ltd. 
 
Tool Appearance, Specifications, and Name 
Application of Anaerobic Glue in Engineering Machinery. 
b: The pressure gauge and leather hose should be used especially for R410A, the 
measurement range of the pressure gauge must be greater than or equal to 4.0 MPa, and the 
tolerance range of the leather hose must be greater than or equal to 4.5 MPa. The size of 
needle valve in the unit is 1/4 inch. Purchase a conversion adapter if you have a different 
size of valve on leather hoses. 
c: The rate flow between 2 L/s and 4 L/s is recommended. Absolute vacuum ≤ 60 Pa. 
d: Dry nitrogen.   
e: A reducing valve needs to install to the outlet of the nitrogen steel vessel, and the 
reducing valve range ≥ 4.0 MPa. 
 
2.7 Personnel Requirements 
Only trained and qualified personnel who fully understand basic safety precautions are 
allowed to install and operate a modular data center. 
 
 
Huawei will not be liable for any consequence caused by the violation of this document. 
The requirements are as follows: 
 
Customers' installation personnel must be trained by Huawei and understand how to 
install and operate a modular data center. 
 
The number of installation personnel varies depending on the project progress and the 
installation environment. Typically, three to five persons are required. 
 
People who need to work at heights must have the required work permit. 
2.8 Scenario Description