No.
Check Item
Result
greater than 1.5 mm.
The cabinets and sealing plates at the ends of the single-row
aisle containment are placed with a front-backward
deviation no greater than 1.5 mm.
4
The height deviation between the floor surface and base top
is within 3 mm, and no deviation is preferred.
□ Passed □ Failed
10.5.1 Installing Sliding Doors (Dual-Row 2000 mm)
Prerequisites
Before installing a sliding door, ensure that the glass panel is not misshapen or damaged and
is 2068 mm (tolerance: ±2 mm) high and 692 mm (tolerance: ±2 mm) wide. If the
requirements are not met, contact Huawei technical support.
Context
Figure 10-22 Sliding door components