EasyManuals Logo

Huawei FusionModule2000 User Manual

Huawei FusionModule2000
318 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #121 background imageLoading...
Page #121 background image
FusionModule2000 Smart Modular Data Center
Installation Guide
10 Installing the Aisle Containment
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
112
No.
Check Item
Result
greater than 1.5 mm.
The cabinets and sealing plates at the ends of the single-row
aisle containment are placed with a front-backward
deviation no greater than 1.5 mm.
4
The height deviation between the floor surface and base top
is within 3 mm, and no deviation is preferred.
â–¡ Passed â–¡ Failed
10.5.1 Installing Sliding Doors (Dual-Row 2000 mm)
Prerequisites
Before installing a sliding door, ensure that the glass panel is not misshapen or damaged and
is 2068 mm (tolerance: ±2 mm) high and 692 mm (tolerance: ±2 mm) wide. If the
requirements are not met, contact Huawei technical support.
Context
Figure 10-22 Sliding door components

Table of Contents

Other manuals for Huawei FusionModule2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000 and is the answer not in the manual?

Huawei FusionModule2000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000
CategoryStorage
LanguageEnglish

Related product manuals